the most trusted name in water testing

K-1682

Drop Test, Neutralizing Amines, Acid-Base Titration, 1 drop = 2.5, 3.8, 4, 5, or 6 ppm

UPC Barcode:
840036011454

$110.15

Analyte System Method/Chemistry Standard/Equivalance or Description Comparator Cell
Neutralizing Amines Drop test Acid-base titration (alkalinity from other sources interferes) 1 drop = 2.5 ppm MEA/3.8 ppm MOPA/3.8 ppm MOR/4 ppm CHA/5 ppm DEAE (DEEA)/6 ppm TEA NA 9198
Test Parameter Description
Alkalinity in steam condensate from system leaks or boiler carryover may cause interference. Also, test cannot be used to find neutralizing amines outside the condensate system where alkalinity from other sources is likely. Neutralizing Amine

REAGENT SHELF LIFE

All reagents have a shelf life, whether they are liquids, powders, crystals, tablets, or test-strip pads. If kept dry, powders and crystals are very stable; acids are also long lived. Date of manufacture is not the controlling factor when it comes to shelf life—storage conditions are more important. As with all perishables, reagents are sensitive to environmental influences and will last longer under controlled conditions.

To this end, we recommend:

  • Storing reagents at a consistent temperature in the range if 36°–85°F (2°–29°C); extreme temperature fluctuation, say from a refrigerator to a hot car trunk, causes reagents to deteriorate.
  • Keeping them out of prolonged direct sunlight. (Note: their brown plastic bottles help protect very light-sensitive reagents.)
  • Segregating reagents from containers of treatment chemicals.
  • Replacing caps immediately and tightening them carefully so that exposure to air and humidity is limited.
  • Avoiding switching bottle caps, placing bottle caps on soiled surfaces, repouring reagents into contaminated containers, or touching test strip pads.

Taylor formulates its reagents to remain effective for at least one year, with only very few exceptions (molybdenum indicator in liquid form is one; after four months old it should be tested against a standard periodically). As a general precaution, replace all reagents more than one year old, or at the beginning of a new testing season.

SDS Documents

Kit Layout

Instructions